06 ELECTRICAL INSTALLATION
3BHS212794 E01 REV M ACS6000 USER MANUAL 156/278
Figure 6-34 Cable route in COU (1000 mm) bottom cable entry
2. Fasten the cables with cable ties.
6.8.6.3 Connecting the cables
Conductors
If a twisted pair cable is used, leave the unshielded cable ends
twisted until they reach the terminals.
Leave unshielded conductor ends as short as possible (not longer
than 50 mm).
Cable shields
Connect the shield of serial communications cables to the
fieldbus adapter.
Connect the individual shields and the overall shield (if present) of
encoder cables to the separate shield grounding point.
IMPORTANT! DO NOT connect the shields to the terminals of
the interface.
Different-sized ground clamps are supplied.
(1) Cable entry bottom
(2) Side view
(3) Detail