3BHS212794 E01 REV M ACS6000 USER MANUAL 217/278
09 CDP CONTROL PANEL
9.2.5.3 Enabling the local lock
• To enable the local lock, set parameter 16.04 to 2 (LOCKED). 
With this parameter setting, local control (including the LOC-REM key) 
is disabled.
If the CDP control panel or a DriveWindow PC is in local control mode 
at the time that the local lock is enabled, they remain in local control 
mode until they are switched to remote control mode. This means that 
the CDP control panel displays the letter L until you press the 
LOC-REM key.
9.2.5.3.1 Disabling the local lock
• To disable the local lock, set parameter 16.04 to 1 (OPEN).
With this parameter setting, switching between remote and local 
control is enabled.
9.2.5.4 Remote control
In remote control mode, operational commands or reference values 
usually come from a higher-level control system via fieldbus or 
remote I/O.
However, with the following parameter settings it is possible to start and 
stop the drive, to set the direction of rotation, and to enter reference 
values from the CDP control panel.
• 11.01 EXT1 START/STOP/DIR = 10 (KEYPAD) or
12.03 EXT REF1 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 1 (EXT1)
• 11.02 EXT2 START/STOP/DIR 10 (KEYPAD) or
12.06 EXT REF2 SELECT = 1 (KEYPAD) and
12.02 EXT1/EXT2 SELECT = 2 (EXT2)
• To enter the remote control mode, press the LOC-REM key.
- A blank space indicates full remote control from a higher-level 
control system.
- The letter R indicates partial remote control (some commands 
are enabled locally).
1                     600.0 rpm       0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW
ACT PAR FUNC DRIVE
LOC
I0
RESET REF
ENTER
REM