3BHS212794 E01 REV M ACS6000 USER MANUAL 157/278
06 ELECTRICAL INSTALLATION
Figure 6-35 Shield grounding point for encoder cable on NTAC pulse encoder (A)
and synchronous serial interface (B)
6.8.7 Routing cables in an EXU cabinet
This section applies to a stand-alone EXU.
6.8.7.1 Auxiliary power and control cables
1. Enter the cables through a free hole of the EMC plate.
2. On the length of cable that passes through the cable transit, prepare
the cable according to the following instructions:
Cable entries with EMC plates: 6.8.4 Preparing cables for EMC
plates on page 151
Cable entries with cable glands: 6.8.3 Preparing cables for cable
glands on page 151.
Note: Materials for cable fitting, EMC requirements and sealing are not
supplied for undrilled plates.
(1) Terminals
(1) Shield grounding point
(2) Ground clamp
AB
1
1
2
2
2
3