06 ELECTRICAL INSTALLATION
3BHS212794 E01 REV M ACS6000 USER MANUAL 144/278
6.7.3 Preparing cables for cable glands
Prepare cables with an outer cable screen or shield for EMC bonding
with the metal enclosure of the cabinet as illustrated in Fig. 6-19.
Figure 6-19 Prepare power cables for cable glands
6.7.4 Preparing cables for EMC plates
This section describes how to prepare standard cables for EMC plates as
well as cables for an EXU.
1. Remove the grommets from the entry plate.
2. To ensure proper sealing, cut along the marking that corresponds to
the cable diameter.
(1) Cable gland
(2) Plate
(3) Heat shrinkable termination
(4) Outer cable sheath
(5) Conductor insulation removed to
expose cable shield
(6) Cable screen extension to be
connected to PE ground busbar
(7) Sheath seal
1
2
3
4
5
6
7