09 CDP CONTROL PANEL
3BHS212794 E01 REV M ACS6000 USER MANUAL 216/278
6. To cancel the setting and keep the original setting, press any of the 
mode selection keys. The selected keypad mode is entered.
9.2.5 Local and remote control mode
The local-remote feature of the CDP control panel allows selecting the 
control location of the drive. Possible are:
• Local control (L)
• Remote control (R)
Note: In this context, remote control is not necessarily equivalent to 
higher-level control. For more information, see “9.2.5.4 Remote 
control” on page 217.
9.2.5.1 Local control
In local control mode, full operational control of the drive is enabled from 
the local operator panel. Commands from remote have no effect.
• To enter the local control mode, press the LOC-REM key.
Local control is indicated by the letter L.
9.2.5.2 Disabling / enabling local lock function
Accidental switching from remote control to local control can be 
prevented with the local lock function.
The corresponding parameter is 16.04 LOCAL LOCK and belongs to the 
parameter group 16 SYSTEM CTRL INPUTS.
1 L -> 0.0 rpm
UPLOAD   <= <=
DOWNLOAD    => =>
CONTRAST        6
ACT PAR FUNC DRIVE
LOC
I0
RESET REF
ENTER
REM
1 L ->             600.0 rpm       0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW
ACT PAR FUNC DRIVE
LOC
I0
RESET REF
ENTER
REM