06 ELECTRICAL INSTALLATION
3BHS212794 E01 REV M ACS6000 USER MANUAL 150/278
6.8.2 Preparing cables for sealing modules
For information on installing the sealing modules and using the
compression wedge, see the Roxtec CF16EMC installation instructions in
“Appendix A – Additional manuals”.
Figure 6-25 Cable entry with sealing modules
1. Unscrew the frame.
2. Prepare the cables with an outer cable screen for EMC bonding with
the metal enclosure of the cabinet as illustrated in Fig. 6-26.
Figure 6-26 Preparing control cables for sealing modules
(1) Sealing modules (2) Compression wedge
(1) Sealing module
(2) Conductive foil
(3) Cable sheath removed to
expose cable shield
(4) Conductor screen extension to
connect to PE terminal
1
1
2
4
4