3BHS212794 E01 REV M ACS6000 USER MANUAL 191/278
08 OPERATION
When alarms and faults are not present and the drive is ready, the
INU CDP control panel displays ReadyOn.
4. Press the SUPPLY ON push button on the door of the control unit to
charge the DC link.
The push button flashes during charging.
The status line of the control panel alternates between Charging
and AuxiliaryOn
.
Note: After charging has been finished, the following takes place:
Main circuit breaker closes automatically.
SUPPLY ON push button lights up permanently.
Drives with an ARU:
- The ARU is now ReadyRun.
1 L -> 0.0 rpm
StateINU ReadyOn
DC VOLT 0.00 rpm
PRI VOLT 0 kW
1 L -> 0.0 rpm
StateINU Charging
MOTOR SP 0.00 rpm
POWER 0.0 kW
Alternating display message:
Charging
AuxiliaryOn
1 L -> 0.0 rpm 0
StateINU ReadyRun
MOTOR SP 0.00 rpm
POWER 0.0 kW
1 L -> 4840.0 V 0
StateARU ReadyRun
DC Voltage 4400.0 V
COS PHI 0.2