10 PREVENTIVE AND CORRECTIVE MAINTENANCE
3BHS212794 E01 REV M ACS6000 USER MANUAL 258/278
Figure 10-24 COU filter
Procedure
1. Switch off the protection switch of the cooling fans.
CAUTION! The cooling fans behind the ventilation grids start
automatically when the temperature rises above a preset level.
2. Remove the bolt at the top of the fan cover.
3. Slide the cover up and pull it out of the slots.
4. Turn the cover over and remove the filter mat.
5. Insert the new filter mat and reinstall the ventilation grid.
(1) Ventilation grid
(2) Wire mesh
(3) Filter mat (only for protection
class IP 54)
10 mm
250 mm
250
mm
1 2 3