3BHS212794 E01 REV M ACS6000 USER MANUAL 165/278
06 ELECTRICAL INSTALLATION
6.8.8.2 Routing cables through the REB (WCU)
1. If present, remove the blanking plate.
The plate can either be discarded or used as an entry plate.
2. Route the cable along the WCU side wall, through the cable transit
and to the receiver.
3. To fix the cables to the rails on the side wall, use a screw base with a
cable tie or cable clamps appropriate for fiber optics.
4. To seal the cable entry, use appropriate sealing inserts for the cable
entry frames.
Figure 6-43 REB cable entry
(1) Blanking plate (removed)
1