3BHS212794 E01 REV M ACS6000 USER MANUAL 255/278
10 PREVENTIVE AND CORRECTIVE MAINTENANCE
10.4.10.2 Installing a phase module
1. Check that the busbars (arrows) of the phase module are lubricated.
Note: If necessary, apply a thin layer of the supplied electrical
contact grease.
2. Make sure that the disconnected water hoses, fiber optics and power
supply leads are out of the way before pushing the phase module into
the cabinet.
3. Place the lifting table in front of the cabinet and adjust it to the
required height.
4. Push the phase module slowly towards the back of the cabinet until
the busbars engage with the connectors at the back of the cabinet.
5. Screw in and tighten the bolts.
6. Pull the locking sleeve of the female half of the water hose coupling
back as far as possible.
7. While holding it in this position, push it over the fixed male half of the
coupling until it stops.
8. Let go of the locking sleeve and firmly push the female part against
the male part until the coupling locks home with a click.
9. Reconnect the optical fibers and power supply leads.
NOTICE DO NOT mix up the cables. The identification on the label must
correspond to its counterpart on the phase module. Verify the correct
connection with the corresponding wiring diagram.
10. Fasten the cables with cable ties.

Table of Contents