3BHS212794 E01 REV M ACS6000 USER MANUAL 131/278
06 ELECTRICAL INSTALLATION
6.3.4 EXU cabinet ground connections
It is important that the EXU is properly grounded to maintain safety and
to ensure smooth functioning of the equipment.
Connect the ground to the ground system of the installation site
and to the ground busbar inside the EXU.
Cross-section of the ground cable and the ground connection must
be in compliance with local regulations.
Ground the outer cable screen at both ends of a cable.
At the EXU, ground the cable screen via the conductive sleeve of the
entry plate.
Figure 6-4 Grounding the EXU
6.4 Internal wiring
This section applies to a drive that is delivered as multiple transport units.
Cables for internal wiring are delivered separately. The pre-assembled
cables are fitted with terminal identifications at each end.
All necessary data for each individual connection are specified on the
Converter hardware diagram and the Wiring list in Appendix D
Wiring diagrams.
The data provide information on:
Cable identification
Cable type
Cross-sectional area
Location of terminals
(1) Transformer
(2) EXU
(3) Motor
(4) Ground cable
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
PE
1
2 3
4