03 POWER ELECTRONICS AND CABINET FEATURES
3BHS212794 E01 REV M ACS6000 USER MANUAL 84/278
Figure 3-36 IAC label example
IMPORTANT! The Main Circuit Breaker (MCB) for the drive fulfills the APR 
(Associated Protection Requirement) without the need for additional 
devices. The MCB requirements are described in “2.7 Important note - 
main circuit breaker” on page 47.
3.8 Busbars and grounding
The ACS6000 drive contains busbars for various types of connections.
Figure 3-37 Busbars
3.8.1 AC busbars
The incoming feeder and motor cables are connected to their 
corresponding busbars inside a TEU. In multi-motor drives, several TEUs 
are part of the drive lineup.
Depending on drive configuration, the incoming busbars are 
interconnected with the ARU or the LSU. The outgoing busbars are 
interconnected with the inverter unit(s). Phase designations help 
identifying the busbars.
IAC
IEC 62477-2
3BHB049908R6220
F L R T B APR SCI
A
t
A
2b
0.3 0.3 0.3 - -
2b 2b 1 1 20 kA 0.5 s Yes No
Distance [m]
Internal Arc Classification (IAC) 
ABB Class II