05 MECHANICAL INSTALLATION
5.3.5 Cable duct material
5.3.6 Installation material
Installation material is supplied with the drive in a separate box.
5.3.7 Tools
See “1.12 Tools” on page 40.
5.3.8 Floor preparation
See “Appendix C – Mechanical drawings”.
5.3.9 Floor fixation
The cabinet can be bolted or welded to the floor. For more information,
see “Appendix C – Mechanical drawings”.
5.3.10 Raw water circuit
The incoming and outgoing raw water pipes are connected to the flanges
of the WCU. Installation material such as counter-flanges, bolts, nuts and
seals are supplied. For information on dimensions of the raw water entry
and the flanges, see “Appendix C – Mechanical drawings”.
▲NOTICE
Risk of component damage!
• Use cable ducts of non-flammable material with non-
abrasive surface.
• To prevent dust, humidity and animals from entering the drive,
protect all cable entries and exits of cable ducts.
⚠ CAUTION
Hazardous voltage!
• If you want to weld a cabinet to the floor, connect the earth clamp
of the welder to the PE ground busbar of the drive.