08 OPERATION
3BHS212794 E01 REV M ACS6000 USER MANUAL 198/278
4. Open the power units and localize the defect.
5. Repair the defect or contact support line if needed.
6. Reset the fault on Arc Guard HMI panel.
7. Acknowledge the firing through with parameter 16.26
on the control
panel (only when fault was understood and corrected).