3BHS212794 E01 REV M ACS6000 USER MANUAL 239/278
10 PREVENTIVE AND CORRECTIVE MAINTENANCE
Figure 10-10 Testing the white lamp
2. Check if the LED of digital input DI07 (input module A2531 in COU1)
is lit.
If the LED is lit, the drive control system receives the feedback
signal "grounding switch is closed", but the control system has not
released the doors.
If the LED is not lit, the feedback signal is missing.
3. To open the door, continue with 10.4.7 Emergency release of a door
safety switch on page 240.
Note: For information on the wiring of the control circuit, see:
Converter hardware diagram
Wiring diagram of COU1
For information on the wiring of the discharging circuit and / or the
grounding circuit, see:
Wiring diagram of COU1
Wiring diagram of CBU
(1) Press cap to test the white lamp