KNX control elements and application parameters
Application "Scene actuator"
Product manual 2CKA00xx73xxxxx
195
8-bit scene: A light scene number is sent with 8 bits. The following supplementary
parameter is available:
Value for object x:
Options: Setting option from 1 - 64
RTC operating mode: The RTC operating mode is sent via the communication object. The
following supplementary parameter is available:
Value for object x:
Options: Comfort
Auto
Standby
ECO
Frost/heat protection
Temperature: After the control element is actuated, the device sends the parameterized
temperature value. The following supplementary parameter is available:
Value for object x:
Options: Setting option from 16 - 31
14-byte text: Makes it possible to send any text with a maximum of 15 characters. The
following supplementary parameter is available:
Value for object x:
Options: <Text>
Notice
How many "Object type x" parameters are displayed depends on the setting of
the "Number of participants" parameter.
Notice
Parameter "Value for object x" can only be set for all options if parameter
"Object x is to be changed" is set on "Yes".

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB SmartTouch i-bus KNX and is the answer not in the manual?

ABB SmartTouch i-bus KNX Specifications

General IconGeneral
BrandABB
ModelSmartTouch i-bus KNX
CategoryTouch Panel
LanguageEnglish

Related product manuals