Editing an ARC Filter using Fast Format
To configure the events on the SPC that will trigger the call to the ARC when Fast Format is the
selected protocol:
1. Select Communications > Reporting > Analog ARC > Edit > Filter.
A list of the eight channels is displayed along with the alarm conditions that can be
programmed for each channel.
2. Select the alarm conditions for each channel as required. For a description of each, see
Outputs types and output ports on page155.
3. From the Scope dropdown menu, select System or a specific area to apply your selected
settings.
4. Click the Test button located next to the first channel to test the alarm activation.
The light bulb icon is switched on.
5. Wait approximately five seconds and click the Test button again for the same channel. This
sends a channel restore to the ARC and the light bulb icon is switched off.
6. Continue to test the other channels.
15.11.3.2 EDP Setup
The system has the facility to communicate information to the SPC Com server remotely using
Vanderbilt’s own protocol, the EDP (Enhanced Datagram Protocol). By correctly configuring an EDP
receiver on the system, it can be programmed to automatically make data calls to the SPC Com
server in a remote location whenever events such as alarm activations, tampers, or arming/disarming
occur. The engineer can configure the system to make calls to the remote server via the following
routes:
l
PSTN (PSTN modem required)
l
GSM (GSM modem required)
l
Internet (Ethernet interface)
If using the PSTN network, ensure the PSTN modem is properly installed and functioning correctly
and that a functioning PSTN line is connected to the A, B terminals on the PSTN modem.
If using the GSM network, ensure the GSM module is properly installed and functioning correctly. An
IP connection can be made across the internet to a server with a fixed public IP address.
If an IP connection is required, ensure the Ethernet interface is correctly configured (seeEthernet
interface on page122) and that internet access is enabled at the router.
Adding an EDP Receiver
1. Select Communications > Reporting > EDP.
Max. 8 receivers can be added to the SPC system.
2. Click the Add button.
SPC42/52/53/63 – Installation & Configuration Manual Engineer programming via the browser
© Vanderbilt 2023 238 I-200572
08.12.2023