6.3.8.5.- Alarm status
6.3.8.5.1.- Relay digital outputs
The Latch variable occupies 2 registers.
All other variables occupy 1 register each.
Table 63: Modbus memory map: Alarm status: Relay digital outputs:
Alarm status Relay digital outputs
Configuration variable
Address
Valid data window
Output 1 Output 2
Latch
(1)
7558-7559 756C-756D
0: unlock alarm
1: locked alarm
Connection delay
(2)
755A 756E
Energy meter which indicates the value of
the connection delay variable (ON)
Disconnection delay
(2)
755B 756F
Energy meter which indicates the value of
the disconnection delay variable (OFF)
Alarm activation date: Year
(2)
755C 7570 2013 to 2076
Alarm activation date: Month
(2)
755D 7571 1 to 12
Alarm activation date: Day
(2)
755E 7572 1 to 31
Alarm activation time: Hour
(2)
755F 7573
0 to 23
Alarm activation time: Minutes
(2)
7560 7574
0 to 59
Alarm activation time: Seconds
(2)
7561 7575
0 to 59
Not used 7562 7576
-
Not used 7563 7577
-
Status
(2)
7564 7578
0: No alarm,
1: Active alarm
Alarm status
(2)
7564 7578
0: No alarm,
1: Pre-alarm,
2: Connection or disconnection delay,
3: Alarm,
4: Impulses,
(1)
If the latch option has been programmed in an alarm and it has been activated, the alarm will be unlocked with
this option.
(2)
For these variables only Function 0x04 is implemented: reading registers.
Note: The 14 registers must be read at once (as a group), otherwise it will respond with an
error.