7.7.- PROFIBUS COMMUNICATIONS MODULE
The Probus communications module, M-CVM-AB-Probus, enables communicating the
CVM-B with a Probus network.
7.7.1.- CONNECTION TERMINALS
Table 133: List of terminals, Probus communications module.
Connection terminals
1: Shield 6: P5, 5V supply voltage
3: B, No inverting input/output signal from Probus 8: A, Inverting input/output signal from Probus
5: M5 GND, Data reference potencial
1
6
3
8
5
Figure 193: Probus communications module terminals.
7.7.2.- LEDs
Table 134: List of LEDs, Probus communications module.
LED State Function
BUS ERROR
ON Communications error
OFF Work correctly
BUS ERROR
Figure 194: Probus LED.