If an alarm has not been programmed for the parameter, the pre-alarm and alarm zones shown 
in the bar chart are calculated.
Figure 23: Calculation of the bar chart.
The calculation formulas are:
 Neutral-phase voltage and neutral voltage
      L = Primary rated voltage* 0.9                            H=  Primary rated voltage * 1.1
      Min = L * 0.8                                                 Max = H * 1.2
      PL = L + (( H - L) * 0.1)                                    PH = H - (( H - L) * 0.1)
 Phase-phase voltage
      L = Primary rated voltage* 0.9 * √3                     H =  Primary rated voltage * 1.1 * √3 
 Min = L * 0.8                                                 Max = H * 1.2
 PL = L + (( H - L) * 0.1)                                    PH = H - (( H - L) * 0.1) 
 Current
    L = 0                                                   H = Primary current 
 Min = 0                                               Max = H * 1.2
                       PL  = 0                                                PH = H - (( H - L) * 0.1)
The alarm and pre-alarm zones L are not displayed.
 Power ratings
    L = 0                                 H = Primary rated voltage * Primary current 
 Min = 0                             Max = H * 1.2
                       PL  = 0                              PH = H - (( H - L) * 0.1)
The alarm and pre-alarm zones L are not displayed.
 Frequency  50 Hz
                       L = 45                                           H = 55
                       Min = L * 0.95                                Max = H * 1.05
                       PL = L + (( H - L) * 0.25)                  PH = H - (( H - L) * 0.25)