If an alarm has not been programmed for the parameter, the pre-alarm and alarm zones shown
in the bar chart are calculated.
Figure 23: Calculation of the bar chart.
The calculation formulas are:
Neutral-phase voltage and neutral voltage
L = Primary rated voltage* 0.9 H= Primary rated voltage * 1.1
Min = L * 0.8 Max = H * 1.2
PL = L + (( H - L) * 0.1) PH = H - (( H - L) * 0.1)
Phase-phase voltage
L = Primary rated voltage* 0.9 * √3 H = Primary rated voltage * 1.1 * √3
Min = L * 0.8 Max = H * 1.2
PL = L + (( H - L) * 0.1) PH = H - (( H - L) * 0.1)
Current
L = 0 H = Primary current
Min = 0 Max = H * 1.2
PL = 0 PH = H - (( H - L) * 0.1)
The alarm and pre-alarm zones L are not displayed.
Power ratings
L = 0 H = Primary rated voltage * Primary current
Min = 0 Max = H * 1.2
PL = 0 PH = H - (( H - L) * 0.1)
The alarm and pre-alarm zones L are not displayed.
Frequency 50 Hz
L = 45 H = 55
Min = L * 0.95 Max = H * 1.05
PL = L + (( H - L) * 0.25) PH = H - (( H - L) * 0.25)