Frequency 60 Hz
L = 55 H = 65
Min = L * 0.95 Max = H * 1.05
PL = L + (( H - L) * 0.25) PH = H - (( H - L) * 0.25)
Voltage THD
L = 0 H = 5
Min =0 Max = H * 2
PL = L + (( H - L) * 0.25) PH = H - (( H - L) * 0.25)
The alarm and pre-alarm zones L are not displayed.
Current THD
L = 0 H = 20
Min =0 Max = H * 2
PL = L + (( H - L) * 0.25) PH = H - (( H - L) * 0.25)
The alarm and pre-alarm zones L are not displayed.
Cosine phi and Power factor
L = -0.9 H = 0.9
Min = -Max Max = minor(L or H) * 1.2
PL = L + (( L - H+2) * 0.25) PH = H + (( L - H+2) * 0.25)