e30bh472.10
D
E
A
B
C
A 25 mm B 32 mm
C 38 mm D 50 mm
E 63 mm
Figure 25: Volume of the Pipe with Different Inside Diameters, 25–63 mm
6.4.5 Pressure Drop
6.4.5.1 Pressure Drop and Correction Factors
The pressure drop with 20 °C (68 °F) water was calculated with a 13 mm (0.5 in) pipe of 1 m (3.3 ft) length at inlet and outlet.
The pressure drop with 48 °C (118 °F) antifreeze can be calculated with the help of the graphs by multiplying them by correction factors.
Table 12: Corrections Factors for Pressure Drop with Antifreeze
Antifreeze Correction factor
Ethylene glycol 10% 1.0
Ethylene glycol 20% 1.0
Ethylene glycol 30% 1.0
Ethylene glycol 40% 1.05
Ethylene glycol 50% 1.1
Propylene glycol 10% 1.0
Propylene glycol 20% 1.0
Propylene glycol 30% 1.05
44 | Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A
Design Guide | iC7 Series Liquid-cooled System Modules