Design Guide | iC7 Series Liquid-cooled System Modules
Table 77: Power Loss for INU Modules without Options, Modulator Type 1 (continued)
System module,
2 kHz switching
frequency
System module,
3 kHz switching
frequency
System module,
4 kHz switching
frequency
System module,
6 kHz switching
frequency
+AKFX
(1)
(1)
Model code Frame Rated
curren
t I
L(1/5)
[A]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss to
liquid
[kW]
Power
loss
to air
[kW]
Power
loss
to air
[kW]
iC7-60SLINB5-1640AE
00F_
2xIM1
2L
1640 11.27 0.11 13.03 0.13 14.87 0.15 19.15 0.19 0.19
iC7-60SLINB5-1795AE
00F_
3xIM1
2L
1795 11.11 0.11 12.90 0.13 14.76 0.15 18.77 0.19 0.18
iC7-60SLINB5-2080AE
00F_
3xIM1
2L
2080 13.45 0.13 15.62 0.16 17.84 0.18 22.76 0.23 0.20
iC7-60SLINB5-2300AE
00F_
3xIM1
2L
2300 15.40 0.15 17.84 0.18 20.42 0.20 26.06 0.26 0.23
iC7-60SLINB5-2500AE
00F_
3xIM1
2L
2500 17.29 0.17 20.00 0.20 22.88 0.23 29.30 0.29 0.31
iC7-60SLINB5-2830AE
00F_
4xIM1
2L
2830 18.42 0.18 21.34 0.21 24.46 0.24 31.18 0.31 0.26
iC7-60SLINB5-3050AE
00F_
4xIM1
2L
3050 20.38 0.20 23.61 0.24 26.97 0.27 34.49 0.34 0.31
iC7-60SLINB5-3260AE
00F_
4xIM1
2L
3260 22.34 0.22 25.90 0.26 29.66 0.30 37.98 0.38 0.48
1) DC fuses
10.7.13 Power Losses of INU Modules without Options, Voltage Class B5, Modulator Type 2 –
Optimized
l The specifications for the values in the table
¢ Inverter module
¢ 380–500 V AC (465–800 V DC)
¢ DC voltage 594 V DC
¢ Switching frequency 2, 3, 4, or 6 kHz
¢ Modulator type 2
Danfoss Drives Oy © 2024.03 AJ475942178716en-000101 / 172K2848A | 211