Chapter 7 Optional AccessoriesMH300
7-41
115V Single-phase
Model
Rated Current in
Normal Duty
(Arms)
Without Output AC reactor
With Output AC Reactor
Shielded Cable
(meter)
Non-shielded
cable (meter)
Shielded Cable
(meter)
Non-shielded
cable (meter)
VFD1A6MH11ANSAA
VFD1A6MH11ENSAA
1.8
50 75 75 115
VFD2A5MH11ANSAA
VFD2A5MH11ENSAA
2.7
VFD5A0MH11ANSAA
VFD5A0MH11ENSAA
5.5
Table 7-46
230V Single-phase
Model
Rated Current in
Normal Duty
(Arms)
Without Output AC reactor With Output AC Reactor
Shielded Cable
(meter)
Non-shielded
cable (meter)
Shielded Cable
(meter)
Non-shielded
cable (meter)
VFD1A6MH21ANSAA
VFD1A6MH21ENSAA
VFD1A6MH21AFSAA
1.8
50 75 75 115
VFD2A8MH21ANSAA
VFD2A8MH21ENSAA
VFD2A8MH21AFSAA
3.2
VFD5A0MH21ANSAA
VFD5A0MH21ENSAA
VFD5A0MH21AFSAA
5
VFD7A5MH21ANSAA
VFD7A5MH21ENSAA
VFD7A5MH21AFSAA
8.5
VFD11AMH21ANSAA
VFD11AMH21ENSAA
VFD11AMH21AFSAA
12.5
Table 7-47
230V Three-phase
Model
Rated Current in
Normal Duty
(Arms)
Without Output AC reactor
With Output AC Reactor
Shielded Cable
(meter)
Non-shielded
cable (meter)
Shielded Cable
(meter)
Non-shielded
cable (meter)
VFD1A6MH23ANSAA
VFD1A6MH23ENSAA
1.8
50 75 75 115
VFD2A8MH23ANSAA
VFD2A8MH23ENSAA
3.2
VFD5A0MH23ANSAA
VFD5A0MH23ENSAA
VFD5A0MH23ANSNA
VFD5A0MH23ENSNA
5
VFD7A5MH23ANSAA
VFD7A5MH23ENSAA
8
VFD11AMH23ANSAA
VFD11AMH23ENSAA
12.5
VFD17AMH23ANSAA
VFD17AMH23ENSAA
19.5
VFD25AMH23ANSAA
VFD25AMH23ENSAA
27
VFD33AMH23ANSAA
VFD33AMH23ENSAA
36
100 150 150 225
VFD49AMH23ANSAA
VFD49AMH23ENSAA
51
VFD65AMH23ANSAA
VFD65AMH23ENSAA
69
VFD75AMH23ANSAA
VFD75AMH23AFSAA
81
VFD90AMH23ANSAA
VFD90AMH23AFSAA
102