Chapter 12 Description of Parameter Settings
MH300
01 Basic Parameters
Y
ou can set this parameter during operation.
Motor 1 Maximum Operation Frequency
Motor 2 Maximum Operation Frequency
Motor 3 Maximum Operation Frequency
Motor 4 Maximum Operation Frequency
Default: 60.00 / 50.00
Settings 00.00–599.00 Hz
Determines the drive’s maximum operation frequency range. This setting corresponds to the
maximum value for the analog input frequency setting signal
(0–10 V, 4–20 mA, 0–20 mA, ±10 V).
Motor 1 Rated / Base Frequency
Motor 2 Rated / Base Frequency
Motor 3 Rated / Base Frequency
Motor 4 Rated / Base Frequency
–599.00 Hz
Set this value according to the motor’s rated frequency from the motor’s nameplate. If the motor’s
rated frequency is 60 Hz, set the value to 60 Hz. If the motor’s rated frequency is 50 Hz, set the
value to 50 Hz.
Motor 1 Rated / Base Voltage
Motor 2 Rated / Base Voltage
Motor 3 Rated / Base Voltage
Motor 4 Rated / Base Voltage
220.0 / 440.0
0.0–255.0 V
0.0–510.0 V
Set this value according to the rated voltage of the motor from the motor’s nameplate. If the
motor’s rated voltage is 220 V, set the value to 220.0 V. If the motor’s rated voltage is 200 V, set
the value to 200.0 V.
There are a wide variety of motors, but the power system for each country is different. The
convenient and economical way to solve this problem is to use an AC motor drive, which can deal
with different voltages and frequencies, while supporting the original characteristics and life of the
motor.
Motor 1 Mid-point Frequency 1
–599.00 Hz
Motor 1 Mid-point Voltage 1
5V / 230V models: 0.0–240.0 V
0.0–480.0 V