Chapter 11 Summary of Parameter Settings
MH300
06 Protection Parameters (1)
Pr. Parameter Name Setting Range Default
06-00 Low voltage level
115V / 230V models: 150.0–220.0 V
DC
460V models: 300.0–440.0 V
DC
180.0
360.0
06-01
Over-voltage stall
prevention
0: Disabled
115V / 230V models: 0.0–390.0 V
DC
460V models: 0.0–780.0 V
DC
380.0
760.0
06-02
Selection for over-voltage
stall prevention
0: Traditional over-voltage stall prevention
1: Smart over-voltage stall prevention
2: Traditional over-voltage and smart over-current stall
prevention
3: Smart over-voltage and smart over-current stall
prevention
0
06-03
Over-current stall
prevention during
acceleration
Normal duty: 0–150% (100% corresponds to the rated
current of the drive)
Heavy duty: 0–200% (100% corresponds to the rated
current of the drive)
120
180
06-04
Over-current stall
prevention during
operation
Normal duty: 0–150% (100% corresponds to the rated
current of the drive)
Heavy duty: 0–200% (100% corresponds to the rated
current of the drive)
120
180
06-05
Acceleration / deceleration
time selection for stall
prevention at constant
speed
0: By current acceleration / deceleration time
1: By the 1
st
acceleration / deceleration time
2: By the 2
nd
acceleration / deceleration time
3: By the 3
rd
acceleration / deceleration time
4: By the 4
th
acceleration / deceleration time
5: By automatic acceleration / deceleration
0
06-06
Over-torque detection
selection (motor 1)
0: No function
1: Continue operation after over-torque detection during
constant speed operation
2: Stop after over-torque detection during constant speed
operation
3: Continue operation after over-torque detection during
RUN
4: Stop after over-torque detection during RUN
0
06-07
Over-
(motor 1)
10–250%
(100% corresponds to the rated current of the drive)
120
06-08
Over-torque detection time
(motor 1)
0.1–60.0 sec. 0.1