Chapter 11 Summary of Parameter Settings
MH300
Pr. Parameter Name Setting Range
Default
05-68
No-load current for induction
motor 3 (A)
0.00–Pr.05-64 default
on the
model
05-69
Stator resistance (Rs) for
induction motor 3
0.000–65.535 Ω
on the
model
05-70
Full-load current for
induction motor 4 (A)
10–120% of the rated current
on the
model
05-71
Rated power for induction
motor 4 (kW)
0.00–655.35 kW
on the
model
05-72
Rated speed for induction
motor 4 (rpm)
0–xxxxx rpm
1710 (60 Hz, 4 poles); 1410 (50 Hz, 4 poles)
on the
motor’s
number of
05-73
Number of poles for
induction motor 4
2–20 4
05-74
No-load current for induction
motor 4 (A)
0.00–Pr.05-70 default
on the
model
05-75
Stator resistance (Rs) for
induction motor 4
0.000–65.535 Ω
on the
model