Chapter 11 Summary of Parameter Settings
MH300
11-28
Pr. Parameter Name Setting Range
Default
05-32
Accumulated motor
operation time (days)
0–65535 days 0
05-33
Induction motor (IM) or
permanent magnet
synchronous motor
selection
0: Induction motor
1: SPM
2: IPM
0
05-34
Full-load current for a
permanent magnet
synchronous motor
0–120% of the drives rated current
Depending
on the
model
power
05-35
Rated power for a
permanent magnet
synchronous motor
0.00655.35 kW
Depending
on the
model
power
05-36
Rated speed for a
permanent magnet
synchronous motor
0–65535 rpm 2000
05-37
Number of poles for a
permanent magnet
synchronous motor
0–65535 10
05-39
Stator resistance for a
permanent magnet
synchronous motor
0.00065.535
0.000
05-40
Permanent magnet
synchronous motor Ld
0.00655.35 mH 0.00
05-41
Permanent magnet
synchronous motor Lq
0.00655.35 mH 0.00
05-42
PG offset angle for a
permanent magnet
synchronous motor
0.0360.0
°
0.0
05-43
Ke parameter of a
permanent magnet
synchronous motor
0–65535 (V/krpm) 0
05-64
Full-load current for
induction motor 3 (A)
10120% of the drives rated current
Depending
on the
model
power
05-65
Rated power for induction
motor 3 (kW)
0.00655.35 kW
Depending
on the
model
power
05-66
Rated speed for induction
motor 3 (rpm)
0–xxxxx rpm
1710 (60 Hz, 4 poles); 1410 (50 Hz, 4 poles)
Depending
on the
motor’s
number of
poles
05-67
Number of poles for
induction motor 3
2–20 4