EasyManua.ls Logo

Delta MH300 Series - 09 Communication Parameters

Delta MH300 Series
1030 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 11 Summary of Parameter Settings
MH300
11-43
09 Communication Parameters
Pr. Parameter Name Setting Range Default
09-00 Communication address 1–254
1
09-01
COM1 transmission speed
4.8115.2 Kbps 9.6
09-02
COM1 transmission fault
treatment
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning, no error displayed and continue operation
3
09-03 COM1 time-out detection 0.0100.0 sec.
0.0
09-04
COM1 communication
protocol
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
1
09-09
Communication response
delay time
0.0200.0 ms 2.0
09-10
Communication main
frequency
0.00599.00 Hz 60.00
09-11 Block transfer 1 0–65535 0
09-12 Block transfer 2 0–65535 0
09-13 Block transfer 3 0–65535 0
09-14 Block transfer 4 0–65535 0
09-15 Block transfer 5 0–65535 0
09-16 Block transfer 6 0–65535 0
09-17 Block transfer 7 0–65535 0
09-18 Block transfer 8 0–65535 0
09-19 Block transfer 9 0–65535 0
09-20 Block transfer 10 0–65535 0

Table of Contents

Related product manuals