Chapter 11 Summary of Parameter Settings
MH300
11-43
09 Communication Parameters
Pr. Parameter Name Setting Range Default
09-00 Communication address 1–254
1
09-01
COM1 transmission speed
4.8115.2 Kbps 9.6
09-02
COM1 transmission fault
treatment
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning, no error displayed and continue operation
3
09-03 COM1 time-out detection 0.0100.0 sec.
0.0
09-04
COM1 communication
protocol
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
1
09-09
Communication response
delay time
0.0200.0 ms 2.0
09-10
Communication main
frequency
0.00599.00 Hz 60.00
09-11 Block transfer 1 0–65535 0
09-12 Block transfer 2 0–65535 0
09-13 Block transfer 3 0–65535 0
09-14 Block transfer 4 0–65535 0
09-15 Block transfer 5 0–65535 0
09-16 Block transfer 6 0–65535 0
09-17 Block transfer 7 0–65535 0
09-18 Block transfer 8 0–65535 0
09-19 Block transfer 9 0–65535 0
09-20 Block transfer 10 0–65535 0