Chapter 11 Summary of Parameter Settings
MH300
Pr. Parameter Name Setting Range Default
08-67
Master and auxiliary
reverse running cutoff
frequency
0.0–100.0% 10.0
08-68 PID deviation limit 0.00–100.00% 0.00
08-69 Integral separation level 0.00–100.00% 0.00
08-70 Smart start-up level 0.00–100.00% 5.00
08-71
Smart start-up frequency
command
0.00–599.00 Hz 0.00
08-72
Smart start-up
acceleration time
0.00–600.00 sec. 3.00
08-75
PID 2 parameter switch
condition
0: Does not switch (refer to Pr.08-01–08-03)
1: Auto-switch is based on output frequency
2: Auto-switch is based on the deviation
0
08-76
PID 2 parameter switch
deviation 1
0.00–Pr.08-77% 10.00
08-77
PID 2 parameter switch
deviation 2
Pr,08-76–100.00% 40.00
08-78
Allowed time to reverse
direction after start-up
0.0–6553.5 sec. 0.0
08-79
WireBreak detected upper
level
0–100% 0
08-80
WireBreak detected lower
level
0–100% 0
08-81 WireBreak detected Time 0.000–65.535 sec. 0.000
08-82 WireBreak treatment
0: Warn and do not stop
1: ramp to stop
2: coast to stop
3: Warn, PID hold
0