Chapter 11 Summary of Parameter Settings
MH300
01 Basic Parameters
Pr. Parameter Name Setting Range Default
01-00
Motor 1 maximum
operation frequency
0.00–599.00 Hz
60.00 /
50.00
01-01
Motor 1 rated / base
frequency
0.00–599.00 Hz
60.00 /
50.00
01-02
Motor 1 rated / base
voltage
115V / 230V models: 0.0–255.0 V
460V series: 0.0–510.0 V
220.0
440.0
01-03
Motor 1 mid-point
frequency 1
0.00–599.00 Hz 3.00
01-04
Motor 1 mid-point voltage
1
115V / 230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
11.0
22.0
01-05
Motor 1 mid-point
frequency 2
0.00–599.00 Hz 1.50
01-06
Motor 1 mid-point voltage
2
115V / 230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
5.0
10.0
01-07
Motor 1 minimum output
frequency
0.00–599.00 Hz 0.50
01-08
Motor 1 minimum output
voltage
115V / 230V models: 0.0–240.0 V
460V series: 0.0–480.0 V
1.0
2.0
01-09 Start-up frequency 0.00–599.00 Hz 0.50
01-10 Upper frequency limit 0.00–599.00 Hz 599.00
01-11 Lower frequency limit 0.00–599.00 Hz 0.00
01-12 Acceleration time 1
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-13 Deceleration time 1
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-14 Acceleration time 2
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-15 Deceleration time 2
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-16 Acceleration time 3
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-17 Deceleration time 3
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-18 Acceleration time 4
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-19 Deceleration time 4
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00