Chapter 11 Summary of Parameter Settings
MH300
Pr. Parameter Name Setting Range Default
01-20 JOG acceleration time
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-21 JOG deceleration time
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.00–6000.00 sec.
10.00
01-22 JOG frequency 0.00–599.00 Hz 6.00
01-23
First / Fourth acceleration
/ deceleration exchange
frequency
0.00–599.00 Hz 0.00
01-24
S-curve acceleration
begin time 1
Pr.01-45 = 0: 0.00–25.00 sec.
Pr.01-45 = 1: 0.00–250.00 sec.
0.20
01-25
S-curve acceleration
arrival time 2
Pr.01-45 = 0: 0.00–25.00 sec.
Pr.01-45 = 1: 0.00–250.00 sec.
0.20
01-26
S-curve deceleration
begin time 1
Pr.01-45 = 0: 0.00–25.00 sec.
Pr.01-45 = 1: 0.00–250.00 sec.
0.20
01-27
S-curve deceleration
arrival time 2
Pr.01-45 = 0: 0.00–25.00 sec.
Pr.01-45 = 1: 0.00–250.00 sec.
0.20
01-28
Skip frequency 1
(upper limit)
0.00–599.00 Hz 0.00
01-29
Skip frequency 1
(lower limit)
0.00–599.00 Hz 0.00
01-30
Skip frequency 2
(upper limit)
0.00–599.00 Hz 0.00
01-31
Skip frequency 2
(lower limit)
0.00–599.00 Hz 0.00
01-32
Skip frequency 3
(upper limit)
0.00–599.00 Hz 0.00
01-33
Skip frequency 3
(lower limit)
0.00–599.00 Hz 0.00
01-34 Zero-speed mode
0: Output waiting
1: Zero-speed operation
2: Minimum frequency (refer to Pr.01-07 and Pr.01-41)
0
01-35 Motor 2 output frequency 0.00–599.00 Hz
60.00 /
50.00
01-36 Motor 2 Output voltage
115 / 230 V models: 0.0–255.0 V
460 V models: 0.0–510.0 V
220.0
440.0
01-37
Motor 2 Mid-point
frequency 1
0.00–599.00 Hz 3.00
01-38
Motor 2 mid-point voltage
1
115 / 230 V models: 0.0–240.0 V
460 V models: 0.0–480.0 V
11.0
22.0