Chapter 11 Summary of Parameter Settings
MH300
11-12
Pr. Parameter Name Setting Range Default
01-39
Motor 2 mid-point
frequency 2
0.00599.00 Hz 1.50
01-40
Motor 2 mid-point voltage
2
115 / 230 V models: 0.0240.0 V
460 V models: 0.0480.0 V
5.0
10.0
01-41
Motor 2 Minimum output
frequency
0.00599.00 Hz 0.50
01-42
Motor 2 minimum output
voltage
115 / 230 V models: 0.0240.0 V
460 V models: 0.0480.0 V
1.0
2.0
01-43 V/F curve selection
0: V/F curve determined by Pr.01-0001-08
1: V/F curve to the power of 1.5
2: V/F curve to the power of 2
16: V/F Separated mode (VFSM)
0
01-44
Auto-acceleration /
deceleration setting
0: Linear acceleration and deceleration
1: Auto-acceleration and linear deceleration
2: Linear acceleration and auto deceleration
3: Auto-acceleration and auto-deceleration
4: Linear, stall prevention by auto-acceleration and
deceleration (limited by Pr.01-1201-21)
0
01-45
Time unit for acceleration
/ deceleration and S-curve
0: Unit 0.01 sec.
1: Unit 0.1 sec.
0
01-46 CANopen quick stop time
Pr.01-45 = 0: 0.00600.00 sec.
Pr.01-45 = 1: 0.006000.00 sec.
1.00
01-49 Deceleration method
0: No function
1: Over-voltage energy restriction
2: Traction energy control
0
01-52
Motor 2 maximum
operation frequency
0.00599.00 Hz
60.00/
50.00
01-53
Motor 3 maximum
operation frequency
0.00599.00 Hz
60.00/
50.00
01-54 Motor 3 output frequency 0.00599.00 Hz
60.00/
50.00
01-55 Motor 3 output voltage
115 / 230 V models: 0.0255.0 V
460 V models: 0.0510.0 V
220.0
440.0
01-56
Motor 3 mid-point
frequency 1
0.00599.00 Hz 3.00
01-57
Motor 3 mid-point voltage
1
115 / 230 V models: 0.0240.0 V
460 V models: 0.0480.0 V
11.0
22.0
01-58
Motor 3 mid-point
frequency 2
0.00599.00 Hz 1.50