Chapter 9 Specification
MH300
9-3
9-2 230V Models
230V, single-phase
Frame A B
Model VFD_ _ _ _ _ _ _ _ _SAA
1A6MH21_ _ 2A8MH21_ _
1A6MH21AF 2A8MH21AF
5A0MH21_ _
AN EN AN EN AN EN
Applicable Motor Output (kW) 0.2 0.4 0.2 0.4 0.75
Applicable Motor Output (HP) 1/4 1/2 1/4 1/2 1
Output Rating
*1
Heavy Duty
Rated Output Capacity (kVA) 0.6 1.1 0.6 1.1 1.9
Rated Output Current (A)
1.6
2.8
1.6
2.8
5.0
Carrier Frequency (kHz)
*2
2–15 (Default: 4)
Normal Duty
Rated Output Capacity (kVA) 0.7 1.2 0.7 1.2
2.0
Rated Output Current (A) 1.8 3.2 1.8 3.2 5.2
Carrier Frequency (kHz)
*2
2–15 (Default: 4)
Input Rating
Rated Input
Current (A)
Heav
y Duty 5.1 7.3 5.1 7.3
11.2
Normal Duty 5.8 8.3 5.8 8.3 11.7
Rated Voltage / Frequency Single-phase, 200240 V
AC
(-15%+10%), 50 / 60 Hz
Operating Voltage Range (V
AC
) 170265
Frequency Range (Hz) 4763
Weight (kg) 0.71 0.76 1.34 1.34 1.25
Cooling Method Convective cooling Fan cooling
EMC Filter
Optional
Built-in
Optional
Ingress Protection Rating IP20 IP40
*3
IP20 IP40
*3
IP20 IP20 IP20 IP40
*3
Frame B C
Model VFD_ _ _ _ _ _ _ _ _SAA 5A0MH21AF
7A5MH21_ _
11AMH21_ _
AN EN AF AN EN AF
Applicable Motor Output (kW) 0.75 1.5 2.2
Applicable Motor Output (HP) 1 2 3
Output Rating
*1
Heavy Duty
Rated Output Capacity (kVA) 1.9 2.9
4.2
Rated Output Current (A)
5.0
7.5
11
Carrier Frequency (kHz)
*2
2–15 (Default: 4)
Normal Duty
Rated Output Capacity (kVA) 2.0 3.2 4.8
Rated Output Current (A) 5.2 8.5 12.5
Carrier Frequency (kHz)
*2
2–15 (Default: 4)
Input Rating
Rated Input
Current (A)
Heav
y Duty 11.2 16.5
24.2
Normal Duty 11.7 18.5 27.5
Rated Voltage / Frequency Single-phase, 200240 V
AC
(-15%+10%), 50 / 60 Hz
Operating Voltage Range (V
AC
) 170265
Frequency Range (Hz) 4763
Weight (kg) 1.34 1.24 1.84 1.24 1.84
Cooling Method Fan cooling
EMC Filter
Built-in
Optional
Built-in
Optional
Built-in
Ingress Protection Rating IP20 IP40
*3
IP20 IP40
*3
IP20
Table 9-2
NOTE:
1. The
default is heavy duty mode.
2. The value of the carrier frequency is set in the factory. To increase the carrier frequency, decrease the current.
See the derating curve diagram in Section 9-6.
3. The IP rating of the wiring area (main circuit terminals and control terminals, frame A / B / C / D / E / F) and the