Chapter 11 Summary of Parameter Settings
MH300
02 Digital Input / Output Parameters
Pr. Parameter Name Setting Range Default
02-00
Two-wire / three-wire
operation control
0: No function
1: Two-wire mode 1, power ON for operation control
(M1: FWD / STOP, M2: REV / STOP)
2: Two-wire mode 2, power ON for operation control
(M1: RUN / STOP, M2: FWD / REV)
3: Three-wire, power ON for operation control
(M1: RUN, M2: REV / FWD, M3: STOP)
4: Two-wire mode 1, Quick Start
(M1: FWD / STOP, M2: REV / STOP)
5: Two-wire mode 2, Quick Start
(M1: RUN / STOP, M2: FWD / REV)
6: Three-wire, Quick Start
(M1: RUN, M2: REV / FWD, M3: STOP)
IMPORTANT
1. In Quick Start function, terminal output will keep in
ready status, drive will response to the command
immediately.
2. When using Quick Start function, the output
terminals UVW are with driving voltages in order to
output and respond immediately if a Start command
is given. Do not touch the terminals or modify the
motor wiring to prevent electric shocks.
1
02-01
Multi-function input
command 1 (MI1)
0: No function
0
1: Multi-step speed command 1
02-02
Multi-function input
command 2 (MI2)
2: Multi-step speed command 2
0
3: Multi-step speed command 3
02-03
Multi-function input
command 3 (MI3)
4: Multi-step speed command 4
1
5: Reset
02-04
Multi-function input
command 4 (MI4)
6: JOG operation
[by external control or KPC-CC01 (optional)]
2
7: Acceleration / deceleration speed inhibit
02-05
Multi-function input
command 5 (MI5)
8: 1
st
and 2
nd
acceleration / deceleration time selection
3
9: 3
rd
and 4
th
acceleration / deceleration time selection
02-06
Multi-function input
command 6 (MI6)
10: External fault (EF) input (Pr.07-20)
4
11: Base Block (B.B.) input from external
02-07
Multi-function input
command 7 (MI7)
12: Output stops
0
13: Cancel the setting for auto-acceleration /
auto-deceleration time
02-26
Input terminal of extension
card (MI10)
0
15: Rotating speed command from AVI