Chapter 11 Summary of Parameter Settings
MH300
Pr. Parameter Name Setting Range Default
07-17 Dwell time at deceleration 0.00–600.00 sec.
0.00
07-18
Dwell frequency at
deceleration
0.00–599.00 Hz
0.00
07-19 Fan cooling control
0: Fan is always ON
1: Fan is OFF after AC motor drive stops for one minute.
2: Fan is ON when AC motor drive runs; fan is OFF when
AC motor drive stops.
3: Fan turns ON when temperature (IGBT) reaches
around 60
o
C.
3
07-20
Deceleration of
emergency or forced stop
0: Coast to stop
1: Stop by the 1
st
deceleration time
2: Stop by the 2
nd
deceleration time
3: Stop by the 3
rd
deceleration time
4: Stop by the 4
th
deceleration time
5: System deceleration
6: Automatic deceleration
0
07-21
Automatic energy-saving
selection
0: Disable
1: Enable
0
07-22 Energy-saving gain 10–1000% 100
07-23
Auto voltage regulation
(AVR) function
0: Enable AVR
1: Disable AVR
2: Disable AVR during deceleration
0
07-24
Torque command f
0.001–10.000 sec. 0.050
07-25
Slip compensation filter
time
0.001–10.000 sec.
0.100
07-26 Torque compensation gain
IM: 0–10 (when Pr.05-33 = 0)
PM: 0–5000 (when Pr.05-33 = 1 or 2)
1
07-27 Slip compensation gain 0.00–10.00
0.00
(Default
value is 1.00
in SVC
07-29 Slip deviation level
0.0–100.0%
0: No detection
0
07-30
Slip deviation detection
time
0.0–10.0 sec.
1.0
07-31 Slip deviation action
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
0
07-32
Motor shock
compensation factor
0–10000
1000