Chapter 12 Descriptions of Parameter Settings
MH300
12.1-00-21
In the HOA mode, if the multi-function input terminal (MI) function setting 41 and 42 are OFF, the
drive does not receive any operation command and JOG is invalid.
00-22
Stop Method
Default: 0
Settings
0: Ramp to stop
1: Coast to stop
Determines how the motor is stopped when the drive receives the Stop command.
1. Ramp to stop: the AC motor drive decelerates to 0 or the minimum output frequency (Pr.01-09)
according to the set deceleration time, and then to stop (according to Pr.01-07).
2. Coast to stop: the AC motor drive stops output immediately, and the motor coasts to stop
according to the load inertia.
Use ramp to stopfor the safety of personnel, or to prevent material from being wasted in
applications where the motor must stop immediately after the drive stops. You must set the
deceleration time accordingly.
If idling is allowed, or the load inertia is large, use “coast to stop. For example, blowers,
punching machines and pumps.
00-23
Motor direction control
Default: 0
Settings 0: Enable forward and reverse
1: Disable reverse
2: Disable forward
Enables the AC motor drives to run in the forward and reverse direction. You can use it to prevent
a motor from running in a direction that would cause injury or damage to the equipment.
00-24
Digital Keypad Frequency Command Memory
Default: Read Only
Settings
Read only
If the keypad is the frequency command source, when Lv or Fault occurs, this parameter stores
the current frequency command.