Chapter 12 Description of Parameter Settings
MH300
12.1-02-28
Pr.02-74 and Pr.02-75 can both be changed during RUN.
Pr.02-74 and Pr.02-75 are saved after powering off.
You can choose N.O. (Pr.02-12 bit = 0) or N.C. (Pr.02-12 bit = 1) through the Pr.02-12 MI mode
to trigger the virtual terminals.
Example: Sets Pr.02-75 = 34h to activate MI1, MI3 and MI4.
02-81
EF Activates when the Terminal Count Value Reached
Default: 0
Settings 0: Terminal count value reached, no EF displays (continues operating).
1: Terminal count value reached, EF is active.
02-82
Initial Frequency Command (F) Mode after Stop
Default: 0
Settings 0: Use current Frequency command
1: Use zero Frequency command
2: Refer to Pr.02-83 to set up
02-83
Initial Frequency Command (F) Setting after Stop
Default: 60.00
Settings 0.00599.0 Hz