Chapter 12 Description of Parameter Settings
MH300
AFM Multi-function Output
Default: 0
Settings 0–23
Function Chart
Settings
Functions Descriptions
0 Output frequency (Hz) Maximum frequency Pr.01-00 is processed as 100%.
1 Frequency command (Hz) Maximum frequency Pr.01-00 is processed as 100%.
2 Motor speed (Hz) Maximum frequency Pr.01-00 is processed as 100%.
3 Output current (rms) (2.5 x rated current) is processed as 100%.
4 Output voltage (2 x rated voltage) is processed as 100%.
5 DC bus voltage 450 V (900 V) = 100%
6 Power factor -1.000–1.000 = 100%
7 Power (2 x rated power) is processed as 100%.
8 Output torque Full load torque = 100%
9 AVI 0–10 V = 0–100%
10 ACI 4–20 mA = 0–100%
12 Iq current command (2.5 x rated current) is processed as 100%.
13 Iq feedback value (2.5 x rated current) is processed as 100%.
14 Id current command (2.5 x rated current) is processed as 100%.
15 Id feedback value (2.5 x rated current) is processed as 100%.
16 Vq-axis voltage command 250 V (500 V) = 100%
17 Vd-axis voltage command 250 V (500 V) = 100%
18 Torque command Rated current of motor = 100%
19 PG2 frequency command Maximum frequency Pr.01-00 is processed as 100%.
20 CANopen analog output
For CANopen communication analog output
Terminal Corresponding address
AFM1 2026-A1
AO10 2026-AB
AO11 2026-AC
21 RS-485 analog output
For RS-485 (Modbus) analog output
Terminal Corresponding address
AFM1 26A0H
AO10 26AAH
AO11 26ABH
22
Communication card analog
output
For Communication analog output
(CMM-EIP02, CMM-PD02, CMM-DN02)
Terminal Corresponding address
AFM1 26A0H
AO10 26AAH
AO11 26ABH