Chapter 12 Description of Parameter Settings
MH300
12.1-03-18
03-29
ACI Terminal Input Selection
Default: 0
Settings
0: 420 mA
1: 010 V
2: 020 mA
When you change the input mode, verify that the external terminal switch position (ACI) is
correct.
When you change the setting, proportion to the corresponding AVI and ACI will change to
default.
03-30
PLC Analog Output Terminal Status
Default: Read only
Settings Monitor the status of the PLC analog output terminals
bit 1: AFM
bit 2: AO10
bit 3: AO11
Example:
When Pr.03-30 displays 000Ah (hex) (that is, the value is 10 (decimal) and 1010 (binary)), it
means that AFM and AO11 are used by PLC.
03-31
AFM Output Selection
Default: 0
Settings 0: 010 V output
1: 020 mA output
2: 420 mA output
03-32
AFM DC Output Setting Level
Default: 0.00
Settings 0.00100.00%