Chapter 12 Description of Parameter Settings
MH300
12.1-05-3
05-16
Number of Poles for Induction Motor 2
Default: 4
Settings
2–20
Sets the number of poles for the motor (must be an even number).
Set up Pr.01-35 and Pr.05-15 before setting up Pr.05-04 to make sure the motor operates normally.
05-17
No-load Current for Induction Motor 2 (A)
Default: Depending on the
model power
Settings 0.00Pr.05-13 default
The default is 40% of the motor's rated current.
05-18
Stator Resistance (Rs) for Induction Motor 2
Default: Depending on the
model power
Settings 0.00065.535 Ω
05-19
Rotor Resistance (Rr) for Induction Motor 2
Default: 0.000
Settings 0.00065.535 Ω
05-20
Magnetizing Inductance (Lm) for Induction Motor 2
Default: 0.0
Settings 0.06553.5 mH
05-21
Stator Inductance (Lx) for Induction Motor 2
Default: 0.0
Settings 0.06553.5 mH
05-22
Multi-motors (Induction) Selection
Default: 1
Settings 1: Motor 1
2: Motor 2
3: Motor 3 (VF or SVC control mode only)
4: Motor 4 (VF or SVC control mode only)
Sets the motor operated by the AC motor drive. Multi-motors selection only supports single
control mode. For example, when you set motor 1 as SVC control mode, the control mode of
motors 2–4 are also set as SVC.
05-23
Frequency for Y-connection /
-connection Switch for an Induction Motor
Default: 60.00
Settings 0.00599.00 Hz