Chapter 12 Description of Parameter Settings
MH300
12.1-06-23
corresponds to 75% of the derating ratio. When the output current is higher than the value,
the carrier frequency will not be reduced by this, but if the overload continues for a long
time, the oH1 fault (IGBT overheating) or oL fault (the inverter is overloaded) will be
triggered due to the IGBT temperature rise, and the motor will eventually stop.
The oL protection executes when the current is 120% × 75% = 90% for one minute; therefore,
it must operate by the curve to keep the carrier frequency.
Setting 2:
Actual over-current stall prevention level = derating ratio × over-current stall prevention level
(Pr.06-03 and Pr.06-04).
Rated current derating level: derating ratio × rated current (Pr.00-01).
The protection method and action are set to 0, but this disables the current limit when output
current is the derating ratio x 120% of output current in normal load, and derating ratio x
180% of output current in light load.
The advantage: it can provide a higher starting output current (Pr.06-55 = 0) when the carrier
frequency (Pr.00-17) setting is higher than the default value.
The disadvantage: the carrier frequency derates easily when it overloads.
For example: when Pr.06-55 = 0 or 1, the over-current stall prevention level = Ratio × Pr.06-
03. When Pr.06-55 = 2, the over-current stall prevention level = Pr.06-03.
Use with the settings for Pr.00-16 and Pr.00-17.
The ambient temperature also affects the derating; refer to Section 9-6 Derating for Ambient
Temperature, Altitude and Carrier Frequency.
Example:
Take VFD9A0MH43ANSAA in normal duty for example: ambient temperature 50ºC, UL open-type,
and independent installation. When the carrier frequency is set to 10 kHz, it corresponds to 75%
of the rated output current. The ambient temperature 60ºC corresponds to 75% * 75% of the rated
output current.
06-56
PT100 Voltage Level 1
Default: 5.000
Settings
0.00010.000 V
06-57
PT100 Voltage Level 2
Default: 7.000
Settings 0.00010.000 V
Condition settings: Pr.06-57 > Pr.06-56.
06-58
PT100 Level 1 Frequency Protection
Default: 0.00
Settings 0.00599.00 Hz
06-59
PT100 activation level 1 protection frequency delay time
Default: 60
Settings
0–6000 sec.
PT100 operation instructions