Chapter 12 Description of Parameter Settings
MH300
Motor Shock Compensation Factor
Default: 1000
Settings 0–10000
If there are current wave motions in the motor in some specific area, setting this parameter can
effectively improve this situation.
When the current wave motion occurs in low frequency and high-power, increase the value for
Pr.07-32.
Auto-restart Interval of Fault
Default: 60.0
Settings 0.0–6000.0 sec.
When a reset / restart occurs after a fault, the drive uses Pr.07-33 as a timer and starts counting
the number of faults within this time period. Within this period, if the number of faults does not
exceed the setting for Pr.07-11, the counting clears and starts from 0 when the next fault occurs.
PMSVC Voltage Feed Forward Gain
Default: 1.00
Settings 0.50–2.00
Adjusts the PMSVC voltage feedback forward gain, and to meet the demand of rapid feedback
application.
Pr.07-38 = 1.00 means forward feedback = Ke × motor rotor speed
Refer to Section 12-2 “PMSVC adjustment” for details.
Default: 8000
Settings 0–65535
Default: 150
Settings 0–65535
Sets the PI gain of DC bus voltage controller when the dEb function activates.
If the DC bus voltage drops too fast, or the speed oscillation occurs during deceleration after the
dEb function activates, adjust Pr.07-62 and Pr.07-63. Increase the Kp setting to quicken the control
response, but the oscillation may occur if the setting is too large. Use Ki parameter to decrease
the steady-state error to zero, and increase the setting to quicken the response speed.