Chapter 12 Description of Parameter Settings
MH300
12.1-11-2
bit1=0: no function.
bit1=1: Inertia estimation function is enabled. bit1 setting would not activate the estimation
process, set Pr.05-00=12 to begin FOC / TQC Sensorless inertia estimating.
bit2 = 0: no function.
bit2 = 1: when frequency command is less than Fmin (Pr.01-07), it will use the zero-servo function
as position control.
bit 7 = 0: Save the frequency before power is OFF. When power is ON again, the save frequency
is displayed.
bit 7 = 1: Do not save the frequency before power is OFF. When power is ON again, 0.00 Hz is
the displayed frequency.