Chapter 12 Description of Parameter Settings
MH300
12.1-11-15
bit No. Setting Description
bit2 = 1: Software limit switch function is enabled when the
drive is in multi-step positioning and pulse-train
positioning position control modes
The action of software / hardware switches and control modes:
Control Mode
Setting
IM
VF VFPG SVC FOCPG FOC TQCPG TQC
bit2: SW limit
switch function
enabled
N/A N/A N/A
Warning
displays
N/A
Warning
displays
N/A
bit3: HW limit
switch function
enabled
Error
displays
Error
displays
Error
displays
Warning
displays
Error
displays
Warning
displays
Error
displays
Control Mode
Setting
PM
SynRM
PMSVC FOCPGPM PMFOC HFI PMTQCPG
bit2: SW limit
switch function
enabled
N/A
Warning
displays
N/A N/A
Warning
displays
N/A
bit3: HW limit
switch function
enabled
Error
displays
Warning
displays
Error
displays
Error
displays
Warning
displays
Error
displays
Positioning
Method
Setting
Single-point Pulse-train Homing P2P
bit2: SW limit
switch function
enabled
N/A Warning displays N/A Warning displays
bit3: HW limit
switch function
enabled
Warning displays Warning displays Warning displays Warning displays
The position memory function is available for coordinate system that remains at the mechanical
origin after the drives power-off when using incremental encoder.
For example:
For example, if the motor stops at the absolute position 100000 before power-off, then the
motors initial position remains at 100000 and homing has been completed after the drive is
powered on again. With the position memory function, you do not need to do the homing again.
It is time-saving and more efficient.
The position memory function is valid only when the homing has been completed. Any
incomplete homing cannot work with this function.
The position memory function only works with motor that has braking mechanism. If you move
the motor by hands or by other methods when the drive is powered off, the saved origin will be
different from the actual origin after power resumes because the drive cannot realize the moving
distance during power-off, further causing a risk of collision when executing position commands.
When Pr.11-60 bit1 = 0, the single-turn pulse number refers to encoders Z-phase signal. But the
communication type encoder does not have Z-phase signal, which makes the setting bit1 = 0
unable to position.