Chapter 12 Description of Parameter SettingsMH300
12.2-12
(adjust the acceleration / deceleration time according to the load inertia. The smaller the
load inertia, the shorter the acceleration / deceleration time is set).
(4) Check if the load and the motor is connected.
(5) Set Pr. 11-00 bit1 = 1, inertia estimate (only in FOCPG mode).
(6) Press RUN key to proceed the inertia
Quickly run the motor in forward and reverse direction repeatedly, and observe the inertia
estimated value of Pr. 11-01 for the keypad.
a. If the system inertial estimated value of Pr. 11-01 does not change ( = default 256), it
means the inertia estimation is wrong. Reduce the frequency command and estimate
the inertia again.
b. If the system inertia estimated value of Pr. 11-01 is still a lot different from the estimated
value of FWD/REV operation, continue the estimation in forward / reverse operating
direction to restraint the estimated inertia to small difference.
(7) Press STOP key to obtain the estimated inertia value:
a. Press ENTER to confirm the input value at the displayed page of the last estimated
inertia value of Pr. 11-01.
b. Set Pr.11-01 bit1 = 0, return the control mode to speed mode.
c. Set the acceleration / deceleration time (Pr.01-12, 01-13) back to the default value.