Chapter 13 Warning Codes|MH300
13-13
ID No.
Display Warning Name Description
12
ACI analog signal
loss (AnL)
Analog input current loss (including all analog 420
mA signals)
Action and Reset
Action condition
When the analog input is lower than 4 mA (only detects analog input 4
20 mA)
Action time Immediately act
Warning treatment parameter
Pr.03-19
0: Disable
1: Continue operation at the last frequency (warning, the
keypad displays
“AnL”)
2: Decelerate to 0 Hz (warning, the keypad displays “AnL”)
3: Stop immediately and display ACE
Reset method
Auto
Warning occurs when Pr.03-19=1 or 2. The
Warning
automatically clears when the analog input signal is larger
than
4 mA.
Manual
“Error” occurs when Pr.03-19=3. You must reset manually.
Reset condition Immediately reset
Record Does not record when Pr.03-19=1 or 2 (“Warning”).
Cause Corrective Actions
Loose or broken ACI wiring
Tighten the terminals again.
Replace with a new cable.
External device error Replace with a new device.
Hardware error
If the AnL error still occurs after checking all the wiring, send the drive
back to the factory for repair.

Table of Contents