EasyManua.ls Logo

Delta MH300 Series - Page 673

Delta MH300 Series
1030 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 13 Warning Codes|MH300
13-24
ID No.
Display Warning Name Description
24
Over slip warning
(oSL)
Over slip warning.
By using the maximum slip (Pr.10-
29) as the base,
when the drive outputs at constant speed, and the
F>H or F<H exceeds Pr.07-29 level and Pr.07-
30
setting time, 100% Pr.07-29 = Pr.10-29.
Action and Reset
Action level
When the drive outputs at constant speed, and F>
H or F<H exceeds the
Pr.07-29 level
Action time Pr.07-30
Warning setting parameter
Pr.07-31=0 Warning
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Reset method
When Pr.07-
31=0 and when the drive outputs at constant speed, and F>H
or F<H no longer exceeds the Pr.07-
29 level, the oSL warning
automatically clears.
Reset condition N/A
Record N/A
Cause Corrective Actions
Check if the motor paramete
r is
correct
Check the motor parameter.
The load is too large Decrease the loading.
Check if the settings for Pr.07-
29, Pr.07-30 and Pr.10-29 are
properly set
Check the parameter settings for oSL protection.

Table of Contents