Loading...
Chapter 13 Warning Codes|MH300
13-47
ID No.
Display Warning Name Description
57
No end command
(PLEd)
PLC end command is missing
Action and Reset
Action condition
The “End” com
mand is missing until the last command is executed, the
PLEd warning shows
Action time Immediately displays when the fault is detected
Warning setting parameter NA
Reset method
Check if the program is correct and re-download the program. If the
fault
does not exist, the warning automatically clears.
Reset condition N/A
Record N/A
Cause Corrective Actions
There is no ENDcommand
during PLC operation
1. Disable PLC
2. Remove PLC program (Pr.00-02 = 6)
3. Enable PLC
4. Re-download PLC program