Chapter 14 Fault CodesMH300
The length of motor cable is
long.
Increase the AC motor drive’s capacity.
Install AC reactor(s) on the output side (U/V/W).
Hardware failure
The ocd
occurs due to short circuit or ground fault at the output side of
the drive.
Check for possible short circuits between terminals with the
meter:
B1 corresponds to U, V, W; DC- corresponds to U, V, W;
to U, V, W.
If short circuits occur, return to the factory for repair.
Check if the setting for stall
prevention is correct.
Set the stall prevention to the proper value.